The picture above shows an external floating roof with the roof legs in the high position in this position there is typically about 6 of space between the floor and roof.
Internal floating roof tank legs.
Our maintenance teams can replace damaged legs seal weld pontoons repair leaks replace your outer rim and more.
The floating roof must be provided with landing legs that are designed to support the external floating roof under a uniform design load of at least 25 psf api 650 appendix c 3 10.
The length of the legs must be adjustable from the top of the roof and the legs must be notched or perforated at the bottom to provide drainage.
The altech ifr has supporting legs which are adjustable from the topside while in service.
For more than four decades advance tank has repaired and installed internal and external floating roofs that range from 15 to 300 in diameter.
At low liquid levels the roof eventually lands and a vapor space forms between the liquid surface and the roof similar to a fixed roof tank.
The roof has support legs hanging down into the liquid.
The support legs are usually retractable to increase the working volume of the tank.
Legs are adjustable to the desired normal operating level for each location.
Leg length normally provides at lease 6 0 of clearance between tank and the underside of ifr sheeting for maintenance purposes.
Internal floating roof tank is known as internal floating roof storage tank floating roof oil tank internal floating plate storage tank and internal floating plate oil tank etc.
The interior and exterior of the floating roof support leg boot work together to provide resistance against product loss as well as environmental effects from outside the tank.
Specifically it is an environment friendly and economical storage tank or oil tank installed a floating roof under the vault of the tank usually made of aluminum stainless steel or other material to prevent the.